NGC brings rack-level liquid cooling for existing data centres to Data Centre World London

Next Generation Cooling Ltd Stand: D170
Next Generation Cooling
NGC brings rack-level liquid cooling for existing data centres to Data Centre World London
NGC’s rear-door heat exchanger mounted on an existing rack.
Next Generation Cooling (NGC) will exhibit at Data Centre World London, part of Tech Show London, on 10 and 11 March 2027 at ExCeL London. On stand D170, NGC’s engineers will show how rear-door heat exchangers and Coolant Distribution Units can take existing data centres from air to liquid cooling without rebuilding, and how higher return temperatures cut the energy used for cooling. 
AI is pushing rack densities beyond what room-level air cooling was designed for. For many operators, the question is no longer whether to move towards liquid cooling, but how to do it in a building that is already running.

At Data Centre World London on 10 and 11 March 2027, Next Generation Cooling (NGC) will show its answer: cooling at the rack, engineered for efficiency, stability and existing facilities.

Cooling at the source
NGC’s rear-door heat exchanger mounts directly on existing racks. It removes heat at the source, before it reaches the room, and needs no extra white space. That makes it possible to move from air to liquid cooling without rebuilding the facility and without long downtime. The rear door also removes residual heat from chip-cooled servers, the share of heat that direct-to-chip cooling leaves in the air.

Efficient from low to full load
Demonstrated under real operating conditions, NGC’s RDHx solution reaches a pPUE as low as 1.004. A calculated example for the complete cooling system gives 1.035. In a laboratory test, NGC’s 40 kW rear door, including pumps in the secondary circuit, reached a pPUE of 1.018 at full load and 1.004 at 20% load. The rear door is expected to enter operation in Q1 2027.

Warmer water, less energy
With supply temperatures of 22 to 30 °C and return temperatures of up to 56 °C, NGC’s solutions can cut the energy used for cooling by up to 90% compared with room cooling. A higher return temperature means more hours of free cooling and fewer hours with compressor cooling. Where a district heating network or another heat user is nearby, the surplus heat can be reused.

Built for stability
Each door is part of a distributed system. When one door is opened for service, neighbouring doors and CDUs compensate, with N+1 or N+2 redundancy at door level. The system goes from idle to full cooling in under a second, and Load Changer Boost (patent pending) anticipates load changes. NGC’s modular CDUs scale up to 1,200 kW.

Designed in Denmark, produced in the EU
NGC was founded in 2022 in Hinnerup, Denmark. Its solutions are designed in Denmark, produced in the EU and built with European components from suppliers such as Grundfos, Danfoss, Alfa Laval and MODU.

Meet the engineers
NGC works engineer to engineer. Visit stand D170 to discuss your facility with the people who design the systems.